Opposed mode
Two sensors with the same power and range are required for opposed mode. One sensor oper-
ates in this mode as the emitter and the other sensor as the receiver. The devices are positioned
and aligned opposite each other. This makes it possible to double the effective range of the
sensors. The opposed mode is the most reliable operating mode. All objects that interrupt the
sonic wave are detected. Whether a device is to operate as an emitter or receiver is determined
by the wiring.
NOTE
Opposed mode is only possible with devices of the same type.
All connected sensors in opposed mode must have the same power and range. In
opposed mode, only connect sensors with the same ID no. The ID no. is marked on
each device.
The outputs of the sensor connected as the emitter are not available. The receiver only offers
one switching output on pin 4. IO-Link operation is not possible.