Manual LCO EXC3/ADV3 OTD | 03-2020 | 1.2 | en
corridorFUNCTION V2
c
44 / 63
Variable switch-off times
The profiles and their values can be freely adjusted. The values can be adjusted via a connection to a DALI bus.
Commissioning
Activating and deactivating the corridorFUNCTION V2
Activating the corridorFUNCTION V2 via mains voltage
Activating the corridorFUNCTION V2 is simple. If an a.c. voltage of 230 V is applied to the digital interface of the LED Driver for a
period of at least 5 minutes the LED Driver detects the corridorFUNCTION V2 and automatically activates it. Activation is required
only once per device.
There are different procedures for activating by the mains voltage. The requirements are the same in each case.
Requirements:
Procedure Version 1:
Procedure Version 2:
Procedure Version 3: Only possible if the motion sensor offers a manual override option
The LED Driver is correctly installed in the luminaire
_
Input voltage is applied
_
A motion sensor is connected to information DA/N or DA/L
_
Remain in the activation range of the motion sensor for more than 5 minutes
-> The motion sensor detects movement and switches on
-> The corridorFUNCTION V2 is activated automatically after 5 minutes
-> The light value switches to presence level (default: 100 %)
_
Set the run-on time on the motion sensor to a value greater than 5 minutes
_
Remain in the activation range of the motion sensor for a short time
-> The motion sensor detects movement and switches on
-> The corridorFUNCTION V2 is activated automatically after 5 minutes
-> The light value switches to presence value (default: 100 %)
_
Reset the run-on time of the motion sensor to the required value
_
Set the slide switch on the motion sensor to the "Never-Off" function
_
Wait 5 minutes
-> The corridorFUNCTION V2 is activated automatically after 5 minutes
-> The light value switches to presence value (default: 100 %)
_
Reset the slide switch on the motion sensor to the "automatic" function
_