Manual LCO EXC3/ADV3 OTD | 03-2020 | 1.2 | en
corridorFUNCTION V2
c
43 / 63
1.
2.
3.
4.
5.
6.
corridorFUNCTION V2 (only EXC3)
Description
The corridorFUNCTION V2 enables the illuminance to be linked to the presence or absence of people. A conventional relay motion
sensor is connected. The luminous intensity is increased when a person enters the room. When the person leaves the room the motion
sensor switches off after a certain delay and the luminous intensity is automatically reduced.
The corridorFUNCTION V2 is particularly beneficial in applications in which light is needed round the clock for safety reasons, for
example in public buildings, large apartment complexes, car parks, pedestrian underpasses and underground railway stations. Since
the luminous intensity only has to be increased when there is a demand for light, the corridorFUNCTION V2 offers effective lighting
management and helps saving energy and costs. Another benefit of the corridorFUNCTION V2 is the enhanced convenience of
automatic lighting control.
Profile settings:
Standard
profile for activating via 230V on the interface terminal DA/N - DA/L for 5 minutes is
"Never off"
The LED Drivers have different profiles so they can provide the best possible performance in a range of conditions. The profiles are
defined by a series of values:
Fade-in time: the time that starts as soon as the presence of a person is detected. During the fade-in time the luminous intensity
is faded up to the presence value (default: 0s).
Run-on time: the time that starts as soon as the presence of a person is no longer detected. If the presence of a person is
detected again during the run-on time the run-on time is restarted from zero. If no presence is detected during the run-on time
the fade time is started as soon as the run-on time expires.
Fade time: the time during which the luminous intensity is faded from the presence value to the absence value (default: 30s).
Switch off delay: the time during which the absence value is held before the lighting is switched off. Depending on the profile
selected the switch-off delay may have different values or may not be defined (default: "Never Off").
Absence value: the luminous intensity when there is no person present (default: 10 %).
Presence value: the luminous intensity when persons are present (default: 100 %).
½
CAUTION!
To ensure correct operation a sinusoidal mains voltage with a frequency of 50 Hz or 60 Hz is required at the control input.
Special attention must be paid to achieving clear zero crossings. Serious mains faults may impair the operation of switchDIM and
corridorFUNCTION V2.