Manual LCO EXC3/ADV3 OTD | 03-2020 | 1.2 | en
eCLO
c
35 / 63
Parameter
Parameter
Default
value
Description
Min
value
Max
value
Initial timer
value
0 h
The initial timer value is always 0.
The function will be started from this step.
0 h
0 h
Initial
intensity
100 %
Specifies the intensity, with which the function is started.
70 %
100 %
Step 1 - 7
timer value
0 h
For each of the 7 further steps (1 - 7) a separate timer value can be specified.
After the period specified here, the respective intensity of the level (1 - 7) is taken.
The 7 timer values are to be entered as absolute values.
0 h
127,500 h
Step 1 - 7
intensity
100 %
For each of the 7 further steps (1 - 7) an intensity can be specified.
If one of the levels is defined as 100 %, the function is ended at this step.
70 %
100 %
LED burning
hours
0 h
Makes it possible to adjust the burning hours of an LED.
With this, LEDs with different burning hours can be matched to each other when
LEDs are replaced.
0 h
131,070 h
Visual
feedback
Off
If visual feedback is enabled, visual feedback is given as soon as the LED exceeds
the expected LED lamp life.
If the expected LED lamp life is exceeded, the luminaire flashes for 2 seconds after
being switched on.
Off
On
Commissioning
Activating and adjusting the eCLO function
Activating and adjusting the eCLO function via companionSUITE (valid for EXC3 and ADV3)
The eCLO function can be activated and adjusted via companionSUITE.
Further information can be found on the Tridonic homepage at
http://www.tridonic.com/download/help/Overview_en.html
http://www.tridonic.com/download/help/corridorFUNCTION_en.html.
Activating and adjusting the eCLO function via masterCONFIGURATOR (valid only for EXC3)
The eCLO function can be activated and adjusted via the masterCONFIGURATOR.
Further information can be found in the masterCONFIGURATOR manual (see
http://www.tridonic.com/com/en/download/Manual_masterConfigurator_en.pdf
...