Installation
(for qualified installers only)
3 3
© Travis Industries
4080207
100-01185_000
Facing Requirements
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it
does, it is considered a mantel and must meet the mantel requirements listed in this manual.
Face Dimensions
Face
Height
Width
Bottom of Face
Installation Notes
Arched Faces
35-1/2”
21-1/8”
Flush w base of fireplace
Arched top is 25-3/4” radius
Bungalow, T. of L.
35-3/8”
21-1/8”
Flush w base of fireplace
Vict. Lace
35-1/2”
21-1/8”
Flush w base of fireplace
Looking Glass
36-3/4”
23-1/2”
1-1/4”
BELOW
base of fireplace
Cast face is approx. 2” thick
Wilmington
36-3/4”
22-1/8”
1-1/4”
BELOW
base of fireplace
Facing Under 1” Thick
Any material that protrudes
more than 3/4” in front of the
facing is considered a mantel
and must meet the mantel
requirements in this manual.
4-7/8”
30-1/2”
(approx.)
3-1/4”
NOTE: The facing tucks
behind the flanges.
NOTE The facing tucks under the notch at the front
of the fireplace (3/8” above the base of the fireplace).
a
b
c
Recommended Order of Installation We
recommend installing the facing (drywall, tile)
under the notch at the front of the fireplace
(“a”) - then install the sides and top (“b” and
“c”)
The wall trim comes off,
allowing the installer to cover
the drywall edge below the
front edge of the fireplace.
3/8”
Facing Over 1” Thick
•
Facing that protrudes in front of the face above the face (or within 1/2” of each side) must be
made of non-combustible materials.
NOTE
A 3/8" gap above the face is required for face installation and removal.