CNT-SVX11A-EN
43
Appendix
Resistance (
V
V
)
Setpoint (°F)
889.4
50
733.6
58
577.9
66
500
70
422.1
74
344.2
78
266.4
82
188.5
86
110.6
90
Hardwired Setpoint Adjustment
Table 26:
Hardwired setpoint adjustment
Fan Switch Resistance Values
Table 27:
Resistance Values
Resistance (
V
V
)
Switch Position
16,300
High
10,700
Low
2,320
Auto
4,870
Off
Resistance (
V
V
)
Temperature
87.5k
V
0
°
F
74.6k
V
5
°
F
63.8k
V
10
°
F
54.6k
V
15
°
F
46.9k
V
20
°
F
40.4k
V
25
°
F
34.8k
V
30
°
F
30.2k
V
35
°
F
26.2k
V
40
°
F
22.8k
V
45
°
F
20.0k
V
50
°
F
17.5k
V
55
°
F
15.3k
V
60
°
F
13.5k
V
65
°
F
11.9k
V
70
°
F
10.5k
V
75
°
F
Resistance (
V
V
)
Temperature
10.0k
V
77
°
F
9.3k
V
80
°
F
8.2k
V
85
°
F
7.3k
V
90
°
F
6.5k
V
95
°
F
5.8k
V
100
°
F
5.2k
V
105
°
F
4.7k
V
110
°
F
4.2k
V
115
°
F
3.8k
V
120
°
F
3.4k
V
125
°
F
3.1k
V
130
°
F
2.8k
V
135
°
F
2.5k
V
140
°
F
2.3k
V
145
°
F
2.1k
V
150
°
F
Hardwired Thermistor Values
Table 28:
Hardwired 10k
V
thermistor values
Содержание Tracer ZN524
Страница 18: ...18 CNT SVX11A EN Typical wiring diagram Figure 12 Wiring diagram with Waterside Economizer option...
Страница 19: ...CNT SVX11A EN 19 Typical wiring diagram Figure 13 Wiring diagram with Hot Gas Reheat option...
Страница 48: ...48 CNT SVX11A EN Location Identifier...
Страница 49: ...CNT SVX11A EN 49 Location Identifier...
Страница 50: ...50 CNT SVX11A EN Location Identifier...
Страница 51: ...CNT SVX11A EN 51 Location Identifier...