44
CNT-SVX11A-EN
Appendix - Binary
Configuration
Binary input
Function
Configuration
Description
or output
BI 1
Low temp detection
Normally closed
Closed: BIP 1 is Normal (no diagnostic)
Open: BIP 1 is Active (diagnostic)
BI 2
Condensate overflow
Normally closed
Closed: BIP 2 is Normal (no diagnostic)
Open: BIP 2 is Active (diagnostic)
BI 3
Occupancy/Generic
Normally closed
Closed: BIP 3 is Normal (Occupied)
Open: BIP 3 is Active (Unoccupied)
1
Normally open
Open: BIP 3 is Normal (Occupied)
Closed: BIP 3 is Active (Unoccupied)
1
BI 4
Fan status
2
Normally open
When the controller commands the fan on and the binary input
remains open for one minute, BIP is normal (diagnostic).
When the controller commands the fan on and the binary input
closes, BIP is active (no diagnostic).
J1-1
Fan
Normally open
De-energized: Fan off
Energized: Fan on
J1-2
RV
Normally open
De-energized: Heat
Energized: Cool
J1-3
Electric Heat/
Normally open
De-energized: Off
Reheat
Energized: Electric Heat/Reheat active
TB4-1 and TB4-2
Generic binary output
Normally open
De-energized: Output off (de-energized)
Energized: Output on (energized)
1. The occupancy input applications vary for standalone and communicated instances. For more information, see Occupancy arbitration
tables in the Appendix.
2. The fan status device is normally closed during normal fan operation. When the fan is off either from a fan failure or the controller com-
manding the fan off, the binary input device opens.
Binary Configuration
Table 29:
Binary configuration details
Содержание Tracer ZN524
Страница 18: ...18 CNT SVX11A EN Typical wiring diagram Figure 12 Wiring diagram with Waterside Economizer option...
Страница 19: ...CNT SVX11A EN 19 Typical wiring diagram Figure 13 Wiring diagram with Hot Gas Reheat option...
Страница 48: ...48 CNT SVX11A EN Location Identifier...
Страница 49: ...CNT SVX11A EN 49 Location Identifier...
Страница 50: ...50 CNT SVX11A EN Location Identifier...
Страница 51: ...CNT SVX11A EN 51 Location Identifier...