36
CNT-SVX11A-EN
Troubleshooting
Diagnostic
Unit Response
Latching/
Reset
non-latching
Fan—enabled
Valves—enabled
Humidity Input Failure
3
Compressor—enabled
Non-latching
Communicated or manual reset
Reheat—disabled
CO2 Sensor
Fan—enabled
Failure
3
Valves—enabled
Non-latching
Communicated or manual reset
Compressor—enabled
Generic
AIP
No Unit Reaction
Non-latching
Communicated or manual reset
Failure
3
Maintenance
Fan—enabled
Required
Valves—enabled
Non-latching
Communicated or manual reset
Compressor—enabled
Local
Fan—enabled
Fan Mode
Valves—enabled
Non-latching
Communicated or manual reset
Failure
3
Compressor—enabled
Local
Fan—enabled
Setpoint
Valves—enabled
Non-latching
Communicated or manual reset
Failure
3
Outdoor air damper—enabled
Invalid
Fan—disabled
Unit
Valves—disabled
Latching
Communicated or manual reset
Configuration
2
Compressor—disabled
Fans—enabled
Normal
Valves—enabled
Non-latching
N/A
Compressor—enabled
Table 19:
Tracer ZN524 Unit Controller diagnostics - continued
1: The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnostics.
2: During manual output test, these diagnostics make the green status LED flash in a two-blink pattern. For more information see, Manual
Output Test, on page 32.
3: These diagnostics are non-latching and automatically reset when the input is present and valid.
Содержание Tracer ZN524
Страница 18: ...18 CNT SVX11A EN Typical wiring diagram Figure 12 Wiring diagram with Waterside Economizer option...
Страница 19: ...CNT SVX11A EN 19 Typical wiring diagram Figure 13 Wiring diagram with Hot Gas Reheat option...
Страница 48: ...48 CNT SVX11A EN Location Identifier...
Страница 49: ...CNT SVX11A EN 49 Location Identifier...
Страница 50: ...50 CNT SVX11A EN Location Identifier...
Страница 51: ...CNT SVX11A EN 51 Location Identifier...