CNT-SVX11A-EN
47
Appendix -
Data Lists
Table 31:
Input/Output listing
Data Lists
Table 31 provides an input/output list-
ing for the Tracer ZN524 unit controller.
The content of the lists conforms to
both the LonMark Space Comfort
Controller Functional Profile and the
LonMark node object
Table 32:
Configuration properties
Configuration property
SNVT type
SCPT reference
Description
nciSndHrtBt
1
SNVT_time_sec
SCPTmaxSendTime (49)
Send heartbeat
nciSetpoints
1
SNVT_temp_setpt
SCPTsetPnts (60)
Occupancy temperature set
points
nciUnitType
1
SNVT_hvac_type
SCPThvacUnitType (169)
Unit type
nciMinOutTm
SNVT_time_sec
SCPTminSendTime (52)
Minimum send time
nciRcvHrtBt
SNVT_time_sec
SCPTmaxRcvTime (48)
Receive heartbeat
nciLocation
SNVT_str_asc
SCPTlocation (17)
Location label
nciBypassTime
SNVT_time_min
SCPTbypassTime (34)
Local bypass time
nciSpaceRHSetpt
SNVT_lev_percent
SCPThumSetPT(36)
Space RH Setpoint
Input
SNVT type
Output
SNVT type
nviRequest
SNVT_obj_request
nvoStatus
SNVT_obj_status
nviSpaceTemp
1
SNVT_temp_p
nvoFileDirectory
SNVT_address
nviSetpoint
SNVT_temp_p
nvoSpaceTemp
1
SNVT_temp_p
nviSetptOffset
SNVT_temp_p
nvoUnitStatus
1
SNVT_hvac_status
nviOccSchedule
SNVT_tod_event
nvoEffectSetpt
SNVT_temp_p
nviOccManCmd
SNVT_occupancy
nvoEffectOccup
SNVT_occupancy
nviOccSensor
SNVT_occupancy
nvoHeatCool
SNVT_hvac_mode
nviApplicMode
SNVT_hvac_mode
nvoSetpoint
SNVT_temp_p
nviHeatCool
SNVT_hvac_mode
nvoDischAirTemp
SNVT_temp_p
nviFanSpeedCmd
SNVT_switch
nvoLoadAbsK
SNVT_power_kilo
nviComprEnable
SNVT_switch
nvoTerminalLoad
SNVT_lev_percent
nviAuxHeatEnable
SNVT_switch
nvoSpaceRH
SNVT_lev_percent
nviEconEnable
SVNT_switch
nvoOutdoorTemp
SNVT_temp_p
nviEmergOverride
SNVT_hvac_emerg
nvoSpaceCO2
SNVT_ppm
nviSourceTemp
SNVT_temp_p
nvoEnterWaterTemp
SNVT_temp_p
nviSpaceRH
SNVT_lev_percent
nvoLeaveWaterTemp
SNVT_temp_p
nviOutdoorTemp
SNVT_temp_p
1. Required points under Space Comfort Controller profile. All other points are optional.
Содержание Tracer ZN524
Страница 18: ...18 CNT SVX11A EN Typical wiring diagram Figure 12 Wiring diagram with Waterside Economizer option...
Страница 19: ...CNT SVX11A EN 19 Typical wiring diagram Figure 13 Wiring diagram with Hot Gas Reheat option...
Страница 48: ...48 CNT SVX11A EN Location Identifier...
Страница 49: ...CNT SVX11A EN 49 Location Identifier...
Страница 50: ...50 CNT SVX11A EN Location Identifier...
Страница 51: ...CNT SVX11A EN 51 Location Identifier...