46
CNT-SVX11A-EN
Appendix - Unit
Operation
Application
Heat/cool mode input
Effective heat/ cool
Unit Operation
mode input
(nviHeatCool)
mode output
(nviApplicMode)
(nvoHeatCool)
Cool
Any state
Cool
Fan—Enabled
Heating—Disabled
Cooling—Enabled
Damper—Enabled
Pre-cool
Any state
Pre-cool
Fan—Enabled
Heating—Disabled
Cooling—Enabled
Damper—Disabled
Off
Any state
Off
Fan—Disabled
Heating—Disabled
Cooling—Disabled
Damper—Disabled
Test
Any state
Determined by controller
Fan—Enabled
Heating—Enabled
Cooling—Enabled
Damper—Enabled
Fan only
Any state
Fan only
Fan—Enabled
Heating—Disabled
Cooling—Disabled
Damper—Enabled
Note: Night purge, Emergency heat, and Nul modes are not supported by the Tracer ZN524 Unit Controller. If one of these
modes is received by the controller, it is interpreted as Auto.
Table 30:
Unit operation based on H
EAT
/C
OOL
ouput - continued
Содержание Tracer ZN524
Страница 18: ...18 CNT SVX11A EN Typical wiring diagram Figure 12 Wiring diagram with Waterside Economizer option...
Страница 19: ...CNT SVX11A EN 19 Typical wiring diagram Figure 13 Wiring diagram with Hot Gas Reheat option...
Страница 48: ...48 CNT SVX11A EN Location Identifier...
Страница 49: ...CNT SVX11A EN 49 Location Identifier...
Страница 50: ...50 CNT SVX11A EN Location Identifier...
Страница 51: ...CNT SVX11A EN 51 Location Identifier...