12
CNT-SVX11A-EN
Installation & Wiring
Description
Terminals
Function
Range
Zone
TB3-1
Space temperature input
5× to 122×F
(-15× to 50×C)
Ground
TB3-2
Analog ground
NA
Set
TB3-3
Local setpoint input
40× to 115×F
(4.4× to 46.1×C)
Fan
TB3-4
Fan switch input
4821 to 4919
V
(Off)
2297 to 2342
V
(Auto)
15137 to 16463
V
(High)
Ground
TB3-6
Analog ground
NA
Analog Inputs
Table 3:
Analog Inputs (Zone Sensor)
Analog input
Terminal
Function
Range
AI 1
J3 - 1
Entering water temperature or
-40 to 212
0
F (-40
0
to 100
0
C)
J3 - 2
outside air temperature
-40 to 212
0
F (-40
0
to 100
0
C)
AI 2
J3 - 3
Discharge air temperature
-40 to 212
0
F (-40
0
to 100
0
C)
J3 - 4
AI 3
J3 - 5
Leaving water temperature
-40 to 212
0
F (-40
0
to 100
0
C)
J3 - 6
AI 4
J3 - 7
Universal 4-20mA input
4-20ma
J3 - 8
Humidity
0-100%
J3 - 9
CO
2
0 - 2000 ppm
Table 4:
Analog Inputs with terminal connections
1,2
1. Trane Rover service tool uses the unit type to help determine and download the proper default analog input configuration.
2. Analog input 3 (AI 3) configured as generic temperature input does not affect unit operation. When configured, the Tracer
TM
ZN524 unit con-
troller communicates the generic temperature value to Rover or Tracer Summit and displays it as generic temperature.
Содержание Tracer ZN524
Страница 18: ...18 CNT SVX11A EN Typical wiring diagram Figure 12 Wiring diagram with Waterside Economizer option...
Страница 19: ...CNT SVX11A EN 19 Typical wiring diagram Figure 13 Wiring diagram with Hot Gas Reheat option...
Страница 48: ...48 CNT SVX11A EN Location Identifier...
Страница 49: ...CNT SVX11A EN 49 Location Identifier...
Страница 50: ...50 CNT SVX11A EN Location Identifier...
Страница 51: ...CNT SVX11A EN 51 Location Identifier...