CNT-SVX11A-EN
35
Troubleshooting
Diagnostic
Unit Response
Latching/
Reset
non-latching
Fan—off
Auto reset once within 24 hrs.
Valves—closed
If safety generates a diagnostic
High/Low Pressure
Compressor - off
Latching
more than once a communicated
Cutout
2
or manual reset will be
necessary
Fan—off
Low Air Flow/
Valves—closed
Fan Failure
2
Compressors—off
Latching
Communicated or manual reset
Space
Fan—off
Temperature Valves—closed
Failure
2,3
Compressors—off
Non-latching
Communicated or manual reset
Entering
Fan—enabled
Water Temperature
Boilerless control—disabled
Failure
2,3
Waterside Economizer—enabled
Non-latching
Communicated or manual reset
Discharge Air
Fan—on
Auto reset once within 24hrs.
Temperature
Compressor—disable
If safety generates a diagnostic
Limit
Waterside Economizer—enabled
Non-Latching
more than once a communicated
or manual reset will be
necessary.
Discharge Fan—enable
Air Temperature Failure
2,3
Compressors—enabled
Non-latching
Communicated or manual reset
Outdoor Air
Fan—enable
Temperature
Compressor—enable
Non-latching
Communicated or manual reset
Failure
2,3
Table 19:
Tracer ZN524 Unit Controller diagnostics
1: The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnostics.
2: During manual output test, these diagnostics make the green status LED flash in a two-blink pattern. For more information see, Manual
Output Test, on page 32.
3: These diagnostics are non-latching and automatically reset when the input is present and valid.
Содержание Tracer ZN524
Страница 18: ...18 CNT SVX11A EN Typical wiring diagram Figure 12 Wiring diagram with Waterside Economizer option...
Страница 19: ...CNT SVX11A EN 19 Typical wiring diagram Figure 13 Wiring diagram with Hot Gas Reheat option...
Страница 48: ...48 CNT SVX11A EN Location Identifier...
Страница 49: ...CNT SVX11A EN 49 Location Identifier...
Страница 50: ...50 CNT SVX11A EN Location Identifier...
Страница 51: ...CNT SVX11A EN 51 Location Identifier...