Installation & Wiring
CNT-SVX11A-EN
11
Binary input
Pin Location
Function
Configuration
Valid range
BI 1
J2 - 1
24 VAC
Low evaporation temperature
Normally open
J2 - 2
Input
Normally closed
BI 2
J2 - 3
24 VAC
Condensate overflow
Normally open
J2 - 4
Input
Normally closed
BI 3
J2 - 5
24 VAC
Occupancy/Generic
Normally open
J2 - 6
Input
Normally closed
BI 4
J2 - 7
24 VAC
Fan status or not used
Normally open
J2 - 8
Input
Normally closed
1. Trane Rover service tool uses the unit type to help determine and download the proper default binary input configuration.
Binary Inputs
Each binary input associates an input
signal of 0 VAC with open contact and
24 VAC with closed contacts.
Binary Outputs
Outputs are load side switching triacs.
The triac acts as a switch, either making
or breaking the circuit between the load
(valve, damper, contactor, relay) and
ground.
Table 1:
Binary input summary for the J2 terminal board connections
1
Binary Pin
Function
Valid
range
Output
Load
Load
Output
Location
Rating Energized De-Energized
BOP-1
J1-1
Fan
NA
12VA
1 VAC RMS
24 VAC RMS
BOP-2
J1-2
Reversing valve
NA
12VA
1 VAC RMS
24 VAC RMS
BOP-3
J1-3
Electric heat or reheat
NA
12VA
1 VAC RMS
24 VAC RMS
J1-4
(Key)
NA
12VA
1 VAC RMS
24 VAC RMS
BOP-4
J1-5
Compressor 1
Normally open or
12VA
1 VAC RMS
24 VAC RMS
normally closed
2
BOP-5
J1-6
Compressor 2
NA
12VA
1 VAC RMS
24 VAC RMS
BOP-6
J1-9
Isolation valve 1
Normally open or
12VA
1 VAC RMS
24 VAC RMS
normally closed
2
BOP-7
J1-10
Isolation valve 2
4
NA
12VA
1 VAC RMS
24 VAC RMS
BOP-8
J1-11
Economizer valve
NA
12VA
1 VAC RMS
24 VAC RMS
BOP-9
J1-12
Outdoor air damper
NA
12VA
1 VAC RMS
24 VAC RMS
BOP-10
3
TB4-1/
Generic output
NA
12VA
1 VAC RMS
24 VAC RMS
TB4-2
Table 2:
Binary output summary
1
1. Trane Rover service tool uses the unit type to help determine and download the proper default binary output configuration.
2. The normally open/closed configuration item refers to the inactive state of the controller output.
3. BOP-10 is a generic output but requires a 24 VAC source for usage.
4. Typical factory installation has only one (1) ISO valve.
Содержание Tracer ZN524
Страница 18: ...18 CNT SVX11A EN Typical wiring diagram Figure 12 Wiring diagram with Waterside Economizer option...
Страница 19: ...CNT SVX11A EN 19 Typical wiring diagram Figure 13 Wiring diagram with Hot Gas Reheat option...
Страница 48: ...48 CNT SVX11A EN Location Identifier...
Страница 49: ...CNT SVX11A EN 49 Location Identifier...
Страница 50: ...50 CNT SVX11A EN Location Identifier...
Страница 51: ...CNT SVX11A EN 51 Location Identifier...