Appendix - Unit
Operation
Unit Operation Based On The Effective H
EAT
/C
OOL
Output
Table 30:
Unit operation based on H
EAT
/C
OOL
ouput
Application
Heat/cool mode input
Effective heat/ cool
Unit Operation
mode input
(nviHeatCool)
mode output
(nviApplicMode)
(nvoHeatCool)
Auto
Determined by controller
Fan—Enabled
Heating—Enabled
Cooling—Enabled
Damper—Enabled
Heat
Heating
Fan—Enabled
Heating—Enabled
Cooling—Disabled
Damper—Enabled
Morning warm up
Pre-heat
Fan—Enabled
Heating—Enabled
Cooling—Disabled
Damper—Disabled
Cooling
Cooling
Fan—Enabled
Heating—Disabled
1
Cooling—Enabled
Damper—Enabled
Auto
Pre-cool
Pre-cool
Fan—Enabled
Heating—Disabled
1
Cooling—Enabled
Damper—Disabled
Off
Off
Fan—Disabled
Heating—Disabled
Cooling—Disabled
Damper—Disabled
Test
Test
Fan—Enabled
Heating—Enabled
Cooling—Enabled
Damper—Enabled
Fan only
Fan only
Fan—Enabled
Heating—Disabled
Cooling—Disabled
Damper—Enabled
Not present
Determined by controller
Fan—Enabled
Heating—Enabled
Cooling—Enabled
Damper—Enabled
Heat
Any state
Heating
Fan—Enabled
Heating—Enabled
Cooling—Disabled
Damper—Enabled
Morning warm up
Any state
Pre-heat
Fan—Enabled
Heating—Enabled
Cooling—Disabled
Damper—Disabled
Содержание Tracer ZN524
Страница 18: ...18 CNT SVX11A EN Typical wiring diagram Figure 12 Wiring diagram with Waterside Economizer option...
Страница 19: ...CNT SVX11A EN 19 Typical wiring diagram Figure 13 Wiring diagram with Hot Gas Reheat option...
Страница 48: ...48 CNT SVX11A EN Location Identifier...
Страница 49: ...CNT SVX11A EN 49 Location Identifier...
Страница 50: ...50 CNT SVX11A EN Location Identifier...
Страница 51: ...CNT SVX11A EN 51 Location Identifier...