RTAF-SVX001A-EN
9
General Information
The Sintesis RTAF units are helical-rotary type, air-cooled
chillers designed for outdoor installation. The refrigerant
circuits are factory-piped, leak tested and dehydrated.
Every unit is electrically tested for proper control
operation before shipment.
Chilled water inlet and outlet openings are covered for
shipment. The Sintesis RTAF features Trane’s exclusive
Adaptive Control™ logic, which monitors the control
variables that govern the operation of the chiller unit.
Adaptive control logic can adjust capacity variables to
avoid chiller shutdown when necessary, and keep
producing chilled water. The units feature two
independent refrigerant circuits. Each compressor is
controlled by a dedicated variable speed Adaptive
Frequency Drive. Each refrigerant circuit is provided with
filter, sight glass, electronic expansion valve, and charging
valves. The shell-and-tube CHIL™ (Compact-High
performance-Integrated design-Low charge) evaporator is
manufactured in accordance with the ASME standards or
other international codes. Each evaporator is fully
insulated and equipped with water drain and vent
connection.
Units are shipped with full oil charge and can be ordered
with either a factory refrigerant charge or optional
nitrogen charge.
Accessories and Loose Parts
Check all the accessories and loose parts that are shipped
with the unit against the shipping list. Included in these
items will be the water vessel drain plugs, rigging and
electrical diagrams, service literature, which are placed
inside the control panel and/or starter panel for shipment.
If optional elastomeric isolators are ordered with the unit
(model number digit 37=1) they are shipped mounted on
the horizontal support frame of the chiller.