RTAF-SVX001A-EN
13
Dimensions and Weights
Service Clearance
Notes:
•
Area above unit required for operation, maintenance,
panel access and airflow.
NO OBSTRUCTIONS ABOVE UNIT
•
For installations with obstructions or multiple units,
see Close Spacing and Restricted Airflow Bulletin RLC-
PRB037*-EN.
•
Clearance of 78” (1981 mm) on the side of the unit is
required for coil replacement. Preferred side for coil
replacement is shown (right side of unit, as facing
control panel). However, either side is acceptable.
•
A full 36” (914 mm) clearance is required in front of the
control panel. Must be measured from front of panel,
not end of unit base.
•
Clearances shown are sufficient for tube pull.
Unit Dimensions
See unit submittals for specific unit dimensions and water connection locations.
Weights
Figure 2.
RTAF service clearances
Table 3.
Sintesis unit weights
Unit Size (tons)
Shipping Weight
Operating Weight
lb
kg
lb
kg
115
7974
3617
8091
3670
130
8071
3661
8203
3721
150
9467
4294
9628
4367
170
9497
4308
9669
4386
180
9821
4455
10002
4537
200
10829
4912
11012
4995
215
11155
5060
11355
5151