Diagnostics
RTAF-SVX001A-EN
71
Evaporator
Entering Water
Pressure
Evap Entering
Water Pressure
Chiller
Info
Latch
All
Bad Sensor or LLID
Remote
Evaporator
Entering Water
Temperature
Sensor
Evaporator
Entering Water
Temp Sensor
Evap Ent Water
Temp Sensor
Chiller
Normal
Latch
All
Bad Sensor or LLID. Note: Entering Water Temp Sensor is used in EXV
pressure control as well as ice making so it must cause a unit shutdown
even if ice or CHW reset is not installed.
Remote
Evaporator
Isolation Valve
Closed Switch
Failure
Evap Isolation
Valve Closed
Switch Failure
Evap Iso Vlv
Closed Sw Fail
Circuit
Immediate Latch
All
Evaporator isolation valve open limit switch state does not match
expected value. See Evaporator Isolation Valve spec for details.
Local
Evaporator
Isolation Valve
Failed To Close
Evap Isolation
Valve Failed To
Close
Evap Iso Vlv
Failed To Close
Circuit
Immediate Latch
All
Evaporator isolation valve was commanded to close, but limit switches
did not make expected changes within allotted time. See Evaporator
Isolation Valve spec for details.
Local
Evaporator
Isolation Valve
Failed To Open
Evap Isolation
Valve Failed To
Open
Evap Iso Vlv
Failed To Open
Circuit
Immediate Latch
All
Evaporator isolation valve was commanded to open, but limit switches
did not make expected changes within allotted time. See Evaporator
Isolation Valve spec for details.
Local
Evaporator
Isolation Valve
Illegal Switch
State
Evap Isolation
Valve Illegal
Switch State
Evap Iso Vlv
Illegal Sw Stat
Circuit
Immediate Latch
All
Both evaporator isolation valve limit switches were closed at the same
time, which should not be possible. Check for limit switch failure or
improperly adjusted switch points.
Local
Evaporator
Isolation Valve
Open Switch
Failure
Evap Isolation
Valve Open
Switch Failure
Evap Iso Vlv
Open Sw Fail
Circuit
Immediate Latch
All
Evaporator isolation valve closed limit switch state does not match
expected value. See Evaporator Isolation Valve spec for details.
Local
Evaporator
Leaving Water
Pressure
Evap Leaving
Water Pressure
Chiller
Info
Latch
All
Bad Sensor or LLID
Remote
Table 27.
Main processor diagnostics (continued)
Diagnostic
Name
Affects
Target Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level