Diagnostics
RTAF-SVX001A-EN
67
AFD Diagnostics
Table 25.
AFD diagnostics
Diagnostic
Name and
Source
Affects
Target Severity
Persistence
Active Modes
[Inactive
Modes]
Criteria
Reset
Level
AFD Fault - xA Cprsr
Immediate
NonLatch
All
AFD Fault. Numerous drive faults can cause this general fault
including High Pressure Cutout for AFD compressors.
Local
AFD Motor
Current
Overload - xA
Circuit Immediate
Latch
All
Compressor current exceeded overload time vs. trip
characteristic. Must trip = 132% RLA, Must hold=125%
Local
AFD Interrupt
Failure - xA
Chiller
Immediate
Shutdown and
Special Action
Latch
AFD Intended to be
OFF
Respective AFD is reporting that it is still running the
compressor when the MP has commanded the drive/
compressor to be Off. Detection time shall be 10 seconds
minimum and 15 seconds maximum. On detection and until
the controller is manually reset: this diagnostic shall be
active and the alarm relay shall be energized, the Evap Pump
Output will be energized, the effected compressor will be
continually commanded off, and be unloaded, while a normal
stop shall be commanded to all other compressors. For as
long as compressor operation continues, the MP shall
continue oil return and fan control on the circuit affected.
Local