Diagnostics
78
RTAF-SVX001A-EN
Software Error
1002: Call Trane
Service
SW Error 1002-
Call Trane
All
functions
Immediate Latch
All
Reported if state chart misalignment in stopped or inactive state
occurred while a compressor was seen to be operating and this
condition lasted for at least 1 minute (cmprsr operation due to Service
Pumpdown or with Contactor Interrupt Failure diagnostic is excluded).
The presence of this software error message suggests an internal
software problem has been detected. The events that led up to this
failure, if known, should be recorded and transmitted to Trane Controls
Engineering.
Local
Software Error
1003: Call Trane
Service
SW Error 1003-
Call Trane
All
functions
Immediate Latch
All
Reported if state chart misalignment occurred inferred from the
Capacity Control, Circuit, or Compressor State Machines remaining in
the Stopping state for more than 3 minutes. The presence of this
software error message suggests an internal software problem has
been detected. The events that led up to this failure, if known, should
be recorded and transmitted to Trane Controls Engineering.
Local
Starts/Hours
Modified
Starts/Hours
Modified
Cprsr
Info
NonLatch
All
The current value for the cumulative starts and or hours for the given
compressor have been modified by a write override from TU.
Remote
Suction
Refrigerant
Pressure Sensor
- xy
Suction
Pressure Sensor
- xy
Cprsr
Immediate Latch
All
Bad Sensor or LLID
Remote
Unexpected
Starter
Shutdown - xy
Unexpected
Starter Shtdn -
xy
Cprsr
Normal
NonLatch
All Cprsr
Running
modes,
Starting,
Running and
Preparing to
Shutdown
The Starter module status reported back that it is stopped when the MP
thinks it should be running and no Starter diagnostic exist. This
diagnostic will be logged in the active buffer and then automatically
cleared. This diagnostic could be caused by intermittent
communication problems from the Starter to the MP, or due to mis-
binding
Local
Very Low
Evaporator Rfgt
Pressure - xy
Very Low Evap
Rfgt Pressure -
xy
Very Low Evap
Rfgt Press xy
Chiller
Immediate Latch
All
The respective circuit’s evaporator pressure dropped below 80% of the
current Low Evap Refrig Press Cutout setting (see above) or 8 psia,
whichever is less, regardless of the running state of the circuit’s
compressor. Note: Unlike previous products, even if the circuit
associated with the suction pressure sensor is locked out, it will not
defeat the protection afforded by this diagnostic.
Local
Water System
Differential
Pressure
Water System
Diff Pressure
Chiller
Info
Latch
All
Bad Sensor or LLID
Remote
Table 27.
Main processor diagnostics (continued)
Diagnostic
Name
Affects
Target Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level