Start-Up and Shutdown
54
RTAF-SVX001A-EN
Stopped to Starting
Figure 45
shows the timing from a stopped mode to
energizing the first compressor. The shortest allowable
time would be under the following conditions:
•
No motor restart inhibit time left from subsequent
starts
•
Evaporator Water flow occurs quickly with pump on
command
•
Need to cool (differential to start) already exists
The above conditions would allow a compressor to start in
about 20 seconds.
Figure 45.
Sequence of events: stopped to starting