Diagnostics
RTAF-SVX001A-EN
79
Communication Diagnostics
Notes:
•
1The following communication loss diagnostics will
not occur unless that input or output is required to be
present by the particular configuration and installed
options for the chiller.
•
2Communication diagnostics (with the exception of
“Excessive Loss of Comm” are named by the
Functional Name of the input or output that is no
longer being heard from by the Main Processor. Many
LLIDs, such as the Quad Relay LLID, have more than
one functional output associated with it. A comm loss
with such a multiple function board, will generate
multiple diagnostics. Refer to the Chiller's wiring
diagrams to relate the occurrence of multiple
communication diagnostics back to the physical LLID
boards that they have been assigned to (bound).
•
Communication loss diagnostics shall be timed based
on action (target status) and not annunciation on the
operator display.
Table 28.
Communications diagnostics
Diagnostic Name
Affects
Target Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level
Comm Loss: %RLA
Indication Output(Vdc)
Comm: RLA Output
None
Info
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 15-30 second period.
Remote
Comm Loss: Liquid Line
Pressure
Comm: Liquid Line
Pressure
Circuit
Normal
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Oil
Temperature - xy
Comm: Oil Temp - xy
Cprsr
Normal
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: AFD Fault
Input xA
Comm: AFD Fault xA
Cprsr
Normal
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: AFD Run
Command - xA
Comm: AFD Run
Command - xA
Cprsr
Normal
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Auxiliary
Setpoint Command
Comm: Auxiliary Setpt
Cmd
Chiller
Info
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 15-30 second period.
Remote
Comm Loss: Chiller
Bypass Valve Output
Comm: Chiller Bypass
Valve
Chiller
Normal
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Compressor
Discharge Rfgt
Temperature - xy
Comm Loss: Cprsr Disch
Rfgt Temp - xy
Comm: Cprsr Disch Temp
xy
Cprsr
Normal
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Condenser
Fan Enable
Comm: Cond Fan Enable
Circuit
Normal
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Condenser
Fan Enable, Shared
Circuit 1&2
Comm Loss: Cond Fan
Enbl Shared Ckt1&2
Comm: Cond Fan Enbl Ckt
1&2
Circuit
Info
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. This is an
info warning, as it is conceivable that the circuit may run
without the center shared fan deck working if there are many
other coils/fans on the circuits.
Remote