Parameters
Parameter List
Parameter List
Par.
No.
Parameter name:
Default value:
Range:
Conver-
sion type:
Data
type:
8-01
Control Site
Dig. and control word [0]
[0 - 2]
-
5
8-02
Control Word Source
FC Port [1]
[0 - 4]
-
5
8-03
Control Word Timeout Time
600 s
0.1–18000
1
7
8-04
Control Word Timeout Function
Off [0]
[0 - 10]
-
5
8-05
End-of-timeout Function
Hold set-up [0]
[0 - 1]
-
5
8-06
Reset Control Word Timeout
Do not reset [0]
[0 - 1]
-
5
8-07
Diagnosis Trigger
Disable [0]
[0 - 3]
-
5
8-10
Control Word Profile
FC profile [0]
[0 - x]
-
5
8-50
Coasting Select
Logic OR [3]
[0 - 3]
-
5
8-52
DC Brake Select
Logic OR [3]
[0 - 3]
-
5
8-53
Start Select
Logic OR [3]
[0 - 3]
-
5
8-54
Reversing Select
Logic OR [3]
[0 - 3]
-
5
8-55
Set-up Select
Logic OR [3]
[0 - 3]
-
5
8-56
Preset Reference Select
Logic OR [3]
[0 - 3]
-
5
11-00
Neuron ID
00 00 00 00 00 00
-
-
10
11-10
Drive Profile
VSD 6010 [0]
-
-
5
11-15
Lon Warning Word
0
-
-
6
11-18
LonWorks Revision
[0, 10]
-
-
9
11-21
Store Data Values
Off [0]
[0 - 1]
-
5
Parameter Group 8-**
8-01 Control Site
Option:
Function:
The setting in this parameter overrides the settings in par.8-50
to par.8-56
[0] *
Digital and ctrl. word
Control by using both digital input and control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Control word only
Control by using control word only.
8-02 Control Source
Option:
Function:
Select the source of the control word: one of two serial interfaces or four
installed options. During initial power-up, the adjustable frequency drive
automatically sets this parameter to
Option A
[3] if it detects a valid serial
communication bus option installed in slot A. If the option is removed,
the adjustable frequency drive detects a change in the configuration, sets
par.8-02
back to default setting
Adjustable Frequency
Drive Port
, and the adjustable frequency drive then trips. If an option is
installed after initial power-up, the setting of par.8-02
will
TR200 LonWorks
8-1
Содержание LonWorks TR200
Страница 9: ...Copyright 2 2 TR200 LonWorks...
Страница 13: ...Introduction 3 4 TR200 LonWorks...
Страница 21: ...How to install 4 8 TR200 LonWorks...
Страница 45: ...Configuration of the system 5 24 TR200 LonWorks...
Страница 51: ...How to Control the Adjustable Frequency Drive 6 6 TR200 LonWorks...