kWh Counter [kWh]
Variable
name:
SNVT
type:
Value:
nvoDrvEnrg
SNVT_elec_kwh_l
Min.
Max.
Resolution:
0 kWh
219,748,364.8 kWh
1 kWh
This variable contains the power consumption of the motor in kWh measured as a mean value over a one hour
period.
DC Link Voltage [V]
Variable
name:
SNVT
type:
Value:
nvoDCVoltage
SNVT_volt
Min.
Max.
Resolution:
0 V
10,000 V
0.1 V
This variable contains the measured DC link voltage. The value is filtered and therefore may be delayed with up
to 1.3 seconds before a voltage change is reflected in the output variable.
Motor Thermal [%]
Variable
name:
SNVT
type:
Value:
nvoTempMrt
SNVT_lev_cont
Min.
Max.
Resolution:
0
%
100
%
0.5%
This variable contains the calculated / estimated thermal load on the motor.
The cut-out limit is at 100%.
Inverter Thermal [%]
Variable
name:
SNVT
type:
Value:
nvoTempInvrtr
SNVT_lev_cont
Min.
Max.
Resolution:
0
%
100
%
0.5%
This variable contains the percentage thermal load of the inverters.
The cut-out limit is at 100%.
Closed-loop Feedback
Variable
name:
SNVT
type:
Value:
nvoFeedback
SNVT_count_inc_f
Min.
Max.
Resolution:
0 %
100 %
0.5%
This variable contains the summarized amount of network feedback in closed-loop mode.
Configuration of the system
5-10
TR200 LonWorks