Output variables
Variable function
Variable name
SNVT type
Profile
TR200
Par.
Status word
nvoStatusword
SNVT_state
FC VSD
16-03
Drive output [%]
nvoOutputPcnt
SNVT_lev_percent
FC VSD
16-05
Drive output [Hz]
nvoOutputHz
SNVT_freq_hz
FC VSD
16-13
kWh counter
nvoDrvEnrg
SNVT_elec_kwh_l
FC VSD
15-02
DC Link Voltage
nvoDCVoltage
SNVT_volt
FC VSD
16-30
Motor thermal
nvoTempMtr
SNVT_lev_cont
FC VSD
16-18
Inverter Thermal
nvoTempInvrtr
SNVT_lev_cont
FC VSD
16-35
Closed-loop feed-
back
nvoFeedback
SNVT_count_inc_f
FC VSD
16-52
Fan belt broken
nvoBrokenBelt
SNVT_switch
FC VSD
16-93
Alarm flag
nvoAlarm
SNVT_switch
FC VSD
16-90
Warning flag
nvoWarning
SNVT_switch
FC VSD
16-03
Alarm word
nvoAlarmword
SNVT_state_64
FC VSD
16-90 +
16-91
Warning word
nvoWarningword
SNVT_state_64
FC VSD
16-92 +
16-93
Extended status-
word
nvoExtendedStatu-
sword
SNVT_state_64
FC VSD
16-94 +
16-95
Digital inputs
nvoDigitInput
SNVT_state_64
FC VSD
16-60
Analog Input (53)
nvoAnIn1
SNVT_volt/SNVT_amp_mil/
SNVT_lev_percent
FC VSD
16-62
Analog Input (54)
nvoAnIn2
SNVT_volt/SNVT_amp_mil/
SNVT_lev_percent
FC VSD
16-64
Analog Input
(X30/11)
nvo101AnIn1
SNVT_volt/SNVT_lev_percent
FC VSD
16-75
Analog Input
(X30/12)
nvo101AnIn2
SNVT_volt/SNVT_lev_percent
FC VSD
16-76
Analog Input
(X42/1)
nvo109AnIn1
SNVT_volt/SNVT_temp_p/
SNVT_lev_percent
FC VSD
18-30
Analog Input
(X42/3)
nvo109AnIn2
SNVT_volt/SNVT_temp_p/
SNVT_lev_percent
FC VSD
18-31
Analog Input
(X42/5)
nvo109AnIn3
SNVT_volt/SNVT_temp_p/
SNVT_lev_percent
FC VSD
18-32
ECB option status
nvoECBstatus
SNVT_state
FC VSD
31-10
Parameter access
cmd.
nvoParamRes-
ponse
UNVT_param_response
FC VSD
-
Configuration of the system
TR200 LonWorks
5-3
Содержание LonWorks TR200
Страница 9: ...Copyright 2 2 TR200 LonWorks...
Страница 13: ...Introduction 3 4 TR200 LonWorks...
Страница 21: ...How to install 4 8 TR200 LonWorks...
Страница 45: ...Configuration of the system 5 24 TR200 LonWorks...
Страница 51: ...How to Control the Adjustable Frequency Drive 6 6 TR200 LonWorks...