![Trane LonWorks TR200 Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/trane/lonworks-tr200/lonworks-tr200_instruction-manual_1150281027.webp)
Digital / Relay Outputs
Variable
name:
SNVT
type:
State:
nviDigitOutput
SNVT_state_64
Boolean 1 bit x 64
This variable controls the state of the digital outputs and relays.
A logical 1 indicates that the output is on or active.
A logical 0 indicates that the output is off or inactive.
Bit 0
CC Digital Output Terminal 27
Bit 1
CC Digital Output Terminal 29
Bit 2
GPIO Digital Output Terminal X30/6
Bit 3
GPIO Digital Output Terminal X30/7
Bit 4
CC Relay 1 output terminal
Bit 5
CC Relay 2 output terminal
Bit 6
Option B Relay 1 output terminal
Bit 7
Option B Relay 2 output terminal
Bit 8
Option B Relay 3 output terminal
Bit 9-63
Reserved for future terminals
Analog Output (42)
Variable
name:
SNVT
type:
Value:
nviAnOut1
SNVT_lev_percent
Min.:
Max.:
Resolution:
0 %
100 %
0.01%
This variable controls the analog output 42, 0–20 mA or 4–20 mA.
In order to control output 42 via LonWorks, par.6-50
Terminal 42 Output
must be set to one of the following
options:
[139] Bus ctrl. 0–20 mA
[140] Bus crtl. 4–20 mA
[141] Bus crtl. 0–20 mA Timeout
[142] Bus crtl. 4–20 mA Timeout
Function:
Bus crtl. 0–20 mA [139]: The output is controlled via bus. In the event of bus timeout, the output level remains
unchanged.
Bus crtl. 4–20 mA [140]: The output is controlled via bus. In the event of bus timeout, the output level remains
unchanged.
Bus crtl. 0–20 mA [141]: The output is controlled via bus. In the event of bus timeout, the output level is set to
the predefined level in par.6-54
Terminal 42 Output Timeout Preset
.
Bus crtl. 4–20 mA [142]: The output is controlled via bus. In the event of bus timeout, the output level is set to
the predefined level in par.6-54
Terminal 42 Output Timeout Preset
.
Configuration of the system
5-6
TR200 LonWorks
Содержание LonWorks TR200
Страница 9: ...Copyright 2 2 TR200 LonWorks...
Страница 13: ...Introduction 3 4 TR200 LonWorks...
Страница 21: ...How to install 4 8 TR200 LonWorks...
Страница 45: ...Configuration of the system 5 24 TR200 LonWorks...
Страница 51: ...How to Control the Adjustable Frequency Drive 6 6 TR200 LonWorks...