Output Current
Variable
name:
SNVT
type:
Value:
nvoDrvCurnt
SNVT_amp
Min:
Max:
Resolution:
0 A
3,276.6 A
0.1 A
This variable contains the adjustable frequency drive output current in ampere measured as a mean value, IRMS.
The value is filtered and therefore approximately 1.3 seconds delayed before a current change is reflected in the
output variable.
Output Voltage
Variable
name:
SNVT
type:
Value:
nvoDrvVolt
SNVT_volt
Min:
Max:
Resolution:
0
V
3,276.6
V
0.1
V
This variable contains the adjustable frequency drive output voltage.
Output Power
Variable
name:
SNVT
type:
Value:
nvoDrvPwr
SNVT_power_kilo
Min:
Max:
Resolution:
0 kW
6,554.4 kW
0.1 kW
This variable contains the adjustable frequency drive output power in kW, calculated on the basis of the actual
motor voltage and current.
The value is filtered and therefore approximately 1.3 seconds delayed before a power change is reflected in the
output variable.
Running Hours
Variable
name:
SNVT
type:
Value:
nvoDrvRunHours
SNVT_time_hour
Min:
Max:
Resolution:
0 hr
65,534 hr
1 hr
This variable contains the total running hours of the motor.
Configuration of the system
TR200 LonWorks
5-19