Analog Output (X42 /11)
Variable name:
SNVT type:
Value:
nvi109AnOut3
SNVT_lev_percent
Min.:
Max.:
Resolution:
0 %
100 %
0.01%
These variables contain the value allocated to the analog output terminal X42/7-11 of the
Analog I/O option
. The
variable type is changeable with the commissioning tool.
This variable is available only if the Programmable I/O option (MCB 115) has been installed.
Setting of RTC
Variable
name:
SNVT
type:
Field:
nviTimeStamp
SNVT_time_stamp
Year
Month
Day
Hour
Minute
Second
2000 -3000
0 - 12
0 - 31
0 - 23
0 - 59
0 - 59
Use this input to set the built-in Real Time Clock.
ECB Option Mode
Variable
name:
SNVT
type:
State:
nviECBMode
SNVT_state
Boolean 1 bit x 16
Controls the operation mode of the ECB option. The binary value of this variable is mapped directly into par.
31-00
Bypass Mode
.
[0] Drive
[1] Bypass
ECB Remote Bypass Activation
Variable
name:
SNVT
type:
State:
nviECBActivation
SNVT_state
Boolean 1 bit x 16
Controls the remote activation of the ECB option.
The binary value of this variable is mapped directly into par. 31-90.
[0] Disabled
[1] Enabled
This input variable applies only if the ECB option is installed in the adjustable frequency drive.
Configuration of the system
5-8
TR200 LonWorks