![Trane LonWorks TR200 Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/trane/lonworks-tr200/lonworks-tr200_instruction-manual_1150281016.webp)
Maximum Cable Lengths
Network topology
Maximum cable length
Free topology without repeater
1640 ft [500 m]
Free topology with one repeater
3280 ft [1000 m]
Free topology maximum device-to-device
1640 ft [500 m]
Bus topology single terminated
1640 ft [500 m]
Bus topology double terminated without repeater
8858 ft [2700 m]
Bus topology double terminated with one repeater
17716 ft [5400 m]
Bus topology maximum stub length
9.8 ft [3 m]
Use of the same cable type throughout the entire network is recommended in order to avoid impedance mis-
match.
System Specifications
Up to 64 FT-X1/FTT-10 transceivers are allowed per network segment.