Analog Input (X30/12)
Variable
name:
SNVT
type:
Value:
nvo101AnIn2
Changeable
Min.
Max.
Resolution:
SNVT_volt
0 V
10 V
0.1 V
SNVT_lev_percent
0 %
100 %
0.1%
This variable contains the value allocated to the analog input terminal X30/12 of the
General Purpose I/O option,
MCB101
.
If the variable type of SNVT_lev_percent is selected, the relative scaling is from 0 V to par.6-41
Terminal X30/12
High Voltage
.
This variable is available only if the General Purpose I/O option (MCB101) has been installed.
Analog Input (X42/1)
Variable
name:
SNVT
type:
Value:
nvo109AnIn1
Changeable
Min.
Max.
Resolution:
SNVT_volt
0 V
10 V
0.1 V
SNVT_temp_p
-459.67°F
[-273.15°C]
-557.79°F
[-327.66°C]
32.02°F [0.01°C]
SNVT_lev_percent
0 %
100 %
0.1%
Analog Input (X42/3)
Variable
name:
SNVT
type:
Value:
nvo109AnIn2
Changeable
Min.
Max.
Resolution:
SNVT_volt
0 V
10 V
0.1 V
SNVT_temp_p
-459.67°F
[-273.15°C]
-557.79°F
[-327.66°C]
32.02°F [0.01°C]
SNVT_lev_percent
0 %
100 %
0.1%
Analog Input (X42/5)
Variable
name:
SNVT
type:
Value:
nvo109AnIn3
Changeable
Min.
Max.
Resolution:
SNVT_volt
0 V
10 V
0.1 V
SNVT_temp_p
-459.67°F
[-273.15°C]
-557.79°F
[-327.66°C]
32.02°F [0.01°C]
SNVT_lev_percent
0 %
100 %
0.1%
These variables contain the value allocated to the analog input terminal X42/1-5 of the
Analog I/O option,
MCB115
. The variable type is changeable with the commissioning tool.
Configuration of the system
TR200 LonWorks
5-15
Содержание LonWorks TR200
Страница 9: ...Copyright 2 2 TR200 LonWorks...
Страница 13: ...Introduction 3 4 TR200 LonWorks...
Страница 21: ...How to install 4 8 TR200 LonWorks...
Страница 45: ...Configuration of the system 5 24 TR200 LonWorks...
Страница 51: ...How to Control the Adjustable Frequency Drive 6 6 TR200 LonWorks...