![Trane LonWorks TR200 Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/trane/lonworks-tr200/lonworks-tr200_instruction-manual_1150281050.webp)
Bit 09, Local operation / bus control:
Bit 09 set to [0] means that [STOP/RESET] is activated
on the control unit or that Local [2] control in par.
3-13
Reference Site
is selected. It is not possible to
control the adjustable frequency drive via serial com-
munication.
Bit 09 set to [1] means that it is possible to control the
adjustable frequency drive via the serial communica-
tion bus / serial communication interface.
Bit 10, Out of frequency limit:
Bit 10 set to [0] enables the output frequency to reach
the value in par.4-11
Motor Speed Low Limit [RPM]
or par.4-13
Motor Speed High Limit [RPM]
.
Bit 10 set to [1] means that the output frequency is
within the defined limits.
Bit 11, No operation / in operation:
Bit 11 set to [0] means that the motor is not running.
Bit 11 set to [1] means that the adjustable frequency
drive has received a start signal or that the output
frequency is greater than 0 Hz.
Bit 12, Brake OK / Brake warning or failure:
Bit 12 = [0] means that there is no brake warning or
failure present.
Bit 12 = [1] means that the drive has stopped because
of a brake warning or failure.
Bit 13, Voltage OK / limit exceeded:
Bit 13 set to [0] means that there are no voltage warn-
ings.
Bit 13 set to [1] means that the DC voltage in the ad-
justable frequency drive’s intermediate circuit is too
low or too high.
Bit 14, Torque OK / limit exceeded:
Bit 14 set to [0] means that the motor current is lower
than the torque limit selected in par.4-18
Current Lim-
it
.
Bit 14 set to [1] means that the torque limit in par.
4-18
Current Limit
has been exceeded.
Bit 15, Timer OK / limit exceeded:
Bit 15 = [0] means that the timers for motor thermal
protection and inverter thermal protection, respec-
tively, have not exceeded 100%.
Bit 15 = [1] means that one of the timers has exceeded
100%.
How to Control the Adjustable Frequency
Drive
TR200 LonWorks
6-5