LED Behavior
MS: Service LED (red)
Situation
LED
Description
Configured state (Nornal op-
eration)
½ sec. ON, then continously
OFF
The node is configures and
running normally
Non configures state
Flashing ½ Hz
Node is not configures but
has an application. Proceed
with loading node.
Applicationless state
1 sec. ON, 2 sec. OFF, then
continuously ON
Node has no application, the
LonWorks option needs re-
placing or reprogramming
Watchdog resets
Short flash about each 3 sec. Indicates problem with ap-
plication. The LonWorks op-
tion needs replacing
Faulty hardware
Steady ON or OFF
The LonWorks option needs
replacing
NS: Status LED (green)
Situation
LED
Description
Node configured
Steady ON
The node is configured
and running normally
Wink service
Flashing ½ Hz for 20 sec.
Wink service activated in
order to identify node.