Configuration Properties (nci)
Variable function
Variable name
SNVT type
Profile
TR200
parame-
ter
Max. motor speed [%]
nciMaxSpeed
SNVT_lev_percent
VSD 6010
4-13
Min. motor speed [%]
nciMinSpeed
SNVT_lev_percent
VSD 6010
4-11
Nom. motor speed [RPM]
nciNmlSpeed
SNVT_rpm
VSD 6010
1-25
Nom. motor frequency [Hz]
nciNmlFreq
SNVT_freq_hz
VSD 6010
1-23
Min. ramp-up time [s]
nciRampUpTime
SNVT_time_sec
VSD 6010
3-41
Min. ramp-down time [s]
nciRampDownTime
SNVT_time_sec
VSD 6010
3-42
Heartbeat time [s]
nciSndHrtBt
SNVT_time_sec
VSD 6010
-
A range of network configuration variables (SCPTs) is available for configuration of the adjustable frequency
drive parameters. These parameters require setting only once, usually following installation.
Please note that the settings written to configuration properties (NCIs) will be stored in the non-volatile mem-
ory. Continuous writing to configuration properties may damage the non-volatile memory.
Network Variable Description - VSD Profile - input
Adjustable Frequency Drive Speed Setpoint
Variable name:
SNVT type:
State:
Value:
Command:
nviDrvSpeedStpt
SNVT_switch
0 (False)
Any
Stop
1 (True)
0
Running 0%
1 (True)
1-200
Running 0.5% to 100%
1 (True)
201-255
Running 100%
0xFF (default)
Any
AUTO (invalid, no action)
This input variable provides start / stop control and a speed reference.
Network Variable Description - VSD Profile - Output
Drive Speed
Variable
name:
SNVT
type:
Value:
nvoDrvSpeed
SNVT_lev_percent
Min:
Max:
Resolution:
-163.840%
+163.830%
0.005%
This variable contains the adjustable frequency drive speed as a percentage of the nominal speed.
Configuration of the system
5-18
TR200 LonWorks
Содержание LonWorks TR200
Страница 9: ...Copyright 2 2 TR200 LonWorks...
Страница 13: ...Introduction 3 4 TR200 LonWorks...
Страница 21: ...How to install 4 8 TR200 LonWorks...
Страница 45: ...Configuration of the system 5 24 TR200 LonWorks...
Страница 51: ...How to Control the Adjustable Frequency Drive 6 6 TR200 LonWorks...