![Trane Air-Fi WCS-SB Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/trane/air-fi-wcs-sb/air-fi-wcs-sb_installation-operation-and-maintenance-manual_1148928039.webp)
BAS-SVX40K-EN
39
WCS: Network Joining and Controller Association
After addresses are set, insure the network is open, press the center button twice. You will see rotating
segments on the display while the sensor attempts to join the network and associate to the unit
controller. If successful, you will see a signal strength icon.
•
Error code
E2
will appear on the sensor display until the WCS successfully joins the network. Until
network joining is successful, the WCS will repeat its attempt to join every 60 minutes .
•
Association between the WCS and the controller will automatically be initiated. The WCS will repeat
its attempt to associate every 15 minutes until successful. Error code
E1
will be displayed until
association is successful .
•
You can press the center button twice at any time to cause the WCS to re-attempt to join the network
and to associate with the controller.
•
To verify the strength of the network signal quality and of the WCS battery charge, refer to
WCS Signal Quality and Battery Life,” p. 74
.
2% Relative Humidity Sensor Module
A 2% relative humidity (RH) sensor module, available as a separate part (X13790973030; model WCS-
SH), can be installed on a WCS either before or after the WCS is powered up (see below). If the RH
sensor module is installed on the WCS after power-up, the WCS will detect it the next time its backlight
turns on. (The backlight turns on whenever a keypad button is pressed.)
Figure 28.
RH sensor module (WCS-SH)
RH Sensor Module
A WCS with an RH sensor module installed on it will display the humidity measurement icon at the
bottom center of the display as shown in the following figure. The humidity measurement icon alternates
with error codes, if any exist.
Figure 29.
Display screen of a WCS with an RH sensor module
%
WCS : Points and Referencers
If you have added an optional Relative Humidity module or have multiple sensors associated to a single
controller, you may need to add points to be able to see these values in TU or SC. See "Referencing
Individual Sensors" section for more information.