Troubleshooting and Maintenance
This section lists some common problems and their causes, lists network health indicators, and
describes procedures used to maintain a facility.
WCI Does Not Join Network
Problem
Explanation/Resolution
Network closed / Not enough time allowed for
joining
Give the WCI more time to join. If the network closes before the WCI has joined, re-open if necessary by
pressing the OPEN NET button on another member WCI.
Wrong address
For factory addressed WCIs, verify address is correct.
Verify each WCI address after installation.
If sensor is installed, check for error code at sensor.
Initiate network formation and resolve by exception.
No power
Ensure that:
•
The WCI is wired correctly.
•
The corresponding controller is wired to equipment correctly and is powered On.
Too much traffic
Try a different channel by selecting a different net address or by using Tracer TU. A better channel may be
found by trial and error or by using a purchased tool such as WiSpy.
Outside of radio range or too many obstacles
Relocate WCI or add a repeater.
Defective WCI
Replace
Tracer SC+ Does Not Communicate with WCI
Problem
Explanation/Resolution
No power to the WCI
Ensure that the WCI is wired properly to the Tracer SC+
Wireless link on the Tracer SC+ not enabled
Ensure that the wireless link on the Tracer SC+ is enabled and configured to match the WCI address, and
is unique within the building.
One of the devices is outside of radio range
Move network components to within radio range or break up networks to make them smaller so that all
components are within radio range. Alternatively, you can add a repeater to extend the radio range.