![Trane Air-Fi WCS-SB Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/trane/air-fi-wcs-sb/air-fi-wcs-sb_installation-operation-and-maintenance-manual_1148928052.webp)
52
BAS-SVX40K-EN
Possible Cause
Explanation/Resolution
Sensor drains battery
current during sleep (
E3
)
If the error persists and batteries drain prematurely, the sensor may have defective components and
need to be replaced.
Internal failure (
E7
)
Replace the sensor.
Wrong sensor address
(
E8
)
The configured sensor address does not match the sensor address that is expected by the UC. Use
Tracer TU to configure the UC for the quantity of sensors it should accept, if more than one.
Duplicate sensor (
E9
)
Another sensor with the same configured UC address and sensor address is already associated with
the UC. Resolve the duplication. This may involve waiting (up to 34 minutes) for the UC to forget the
address of a failed sensor.
Testing WCS-to-WCI Signal Strength and Battery Life
The WCS-SO, -SCO
2
, -SB/R sensors display the following symbols for signal and battery:
•
S
—Indicates signal strength (from Home screen press UP arrow once).
•
b
—indicates battery life (from Home screen press DOWN arrow once)
The following symbols are appended to the S or b:
Table 9.
Signal strength and battery life symbols
•
Excellent signal quality (Equals green link on the Tracer TU network heath map.)
•
100 — 50% battery life remaining
•
Satisfactory signal quality (Equals yellow link on the Tracer TU network heath
map.)
•
50 — 3% battery life remaining
•
Poor signal quality resulting in unreliable communication (Move sensor or WCI to
a better location, if necessary.)
•
Less than 3% battery life remaining
The following display indicates excellent signal quality::