100
BAS-SVX40K-EN
8. Hit
OK
, then
Send to Device
at the bottom of the MI page. The new point will be sent to SC so it is
available for alarming.
How to Connect Air-Fi® Wireless Sensors Directly to SC+
Tracer SC+ supports sensors connected directly to it since version 5.1. Tracer SC+ supports up to 8
networks with six sensors maximum per network allowing a total number of 48 sensors.
Some applications include:
•
Refrigerator/Freezer monitoring sensor
•
Monitoring sensor for remote area
•
Direct connection to devices that cannot be connected to unit controllers. For example VRF.
Notes:
•
This application only configures sensors directly connected to the SC+. Any Air-Fi sensor
connected to a unit controller must be configured using the Tracer® TU service Tool.
•
Sensor 1 for each network is default enabled.
•
More than 1 sensor per network requires SC+ Configuration.
How to Set-up Air-Fi Network on Tracer Synchrony
1. Address, mount and wire the Air-F® Wireless Communications Interface (WCI) and Air-Fi® Wireless
Communications Sensors (WCSs) according to instructions on the
Air-Fi® Wireless Communication
Interface (WCI) Installation Instructions
(BAS-SVN038*-EN).
2. Open Synchrony and navigate to the Installation menu on the left hand navigator.
3. Select Air-Fi Networks and Sensors link.
4. Select the Create Network button. A new network will be displayed.
5. Edit the BACnet® Network Number if needed. The BACnet® network numbers is provided by
default but can be edited using the pencil icon. BACnet® network numbers should not be duplicated.
6. Click the check icon when finished.
7. Click the trash can icon to delete a network. All sensors in the network will be deleted when the
network is deleted.
Note:
Networks reflected here are all the Air-Fi networks on the SC+ including the WCIs connected to