![Trane Air-Fi WCS-SB Скачать руководство пользователя страница 102](http://html1.mh-extra.com/html/trane/air-fi-wcs-sb/air-fi-wcs-sb_installation-operation-and-maintenance-manual_1148928102.webp)
102
BAS-SVX40K-EN
To change the selection of points, click on the referencer icons.
4. Click the check mark when finished configuring that sensor.
5. Click the trash can icon to delete a sensor.
6. Click the pencil icon to edit the sensor configuration.
Note:
Up to 6 sensors can be directly connected to the SC+ for each network.
Opening Air-Fi Network
1. Ensure that the network is open
2. From Tracer TU, select
“Wireless/Open network”
3. Select the network to open, then click OK
Note:
The network can also be opened at the coordinator by pressing the Open Net button.
Configuring WCS Sensor
1. Hold the Addr button for 3 seconds
2. Set to Group/Net using the up down and next buttons
3. Set the UC Address for 000, not the rotary address of the SC+
4. Select next to set the Sensor# (1-6)
5. Hold the Addr button for 3 seconds to exit addressing mode
6. From a blank display press the up arrow to force the WCS to join the network
Creating Points to the Sensor
1. In Tracer SC+, navigate to
“Points”
, then
“Create Points”
from the top of the Page.
2. Select the point type that is needed for the value, typically
“Analog Input”
.
Figure 66.
Creating points in Tracer SC+
3. Define the Name, Units and select the Referencer.