BAS-SVX40K-EN
47
Important:
The maximum wire length for the external sensor should be limited to 100 feet low capacity
cable (25pf/ft or less).
Note:
If you have more than one sensor associated to the same unit controller, by default the
temperatures will average. This is undesirable if using the external sensor for refrigeration or
freezer monitoring. Some work will be required in Tracer TU to create a new point and remove
the refrigeration temperature from space temperature averaging. See
Temperature Sensor Setup,” p. 93
section in the Using the Tracer® TU Service Tool with a
Wireless Network chapter.
Figure 35.
Sensor cable routing
Field Supplied
10K Type 2
Thermistor
Note:
When installing the WCS-SB/R sensor in a refrigerator or freezer where the temperature may
fluctuate, we recommend using a Thermobuffer to slow down the temperature change. This will
help preserve the battery life of the sensor.