BAS-SVX40K-EN
77
4. Open the network using Tracer TU or by pressing the Open Net button on the WCI coordinator.
5. For WCS-SB/SD sensors, press the center button twice to force the sensor to join the network and
associate to the unit controller. For WCS-SO, -SCO
2
, -SB/R sensors, press the UP arrow once to
force the sensor the join the network and associate to the unit controller. This process may need to
be repeated a few times.
Sensor Output Power Level
The maximum output power level of a wireless sensor set is controlled by software and restricted by
channel of operation and agency requirements per country or region. The sensor has a default
maximum power level of 10 mW, but the WCI determines the ultimate output power level of the sensor.
In North and South America the sensor will change to 100 mW after joining the network.
Cleaning the Sensor
You can clean the sensor by applying glass cleaner to a soft, non-abrasive cloth, and gently wiping the
face, including the buttons and LCD display. Use of a pre-moistened towelette designed for lens or
screen cleaning is also acceptable.
NOTICE
Sensor Damage!
Do not spray glass cleaner or any other solution directly on the sensor as it could damage it.
While you clean it, avoid inadvertent pressing of the keypad buttons on the sensor, as this may result in
an unwanted timed override or settings change.