![Trane Air-Fi WCS-SB Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/trane/air-fi-wcs-sb/air-fi-wcs-sb_installation-operation-and-maintenance-manual_1148928020.webp)
20
BAS-SVX40K-EN
Table 6.
Wireless sensing specifications
Sensor Type
Sampling Rate
Change of Value Trigger/Delay
Heartbeat
Temperature
30 seconds
0.2°F
15 minutes
Relative Humidity
30 seconds
1% RH
CO
2
Occupied — 5 minutes
Unoccupied — 15 minutes
50 ppm
Occupancy
Continuous
Unoccupied to Occupied:
•
Transmits change of state within
30 seconds.
Occupied to Unoccupied:
•
5–10 minutes delay (not
adjustable).
•
Sends unoccupied message
after 5–10 minutes without
motion.