38
BAS-SVX40K-EN
Figure 26.
Setting a unique sensor address
11. Press the up/down arrow button to set a unique sensor address (1 through 6) for the WCS.
12. Addressing is finished. Press the center button to return to the normal display.
Note:
To verify addressing, press and hold the Address button until the display changes to addressing
mode. Then use the right arrow button to scroll through the settings.
The following figure shows the same Air-Fi Wireless figure shown in
, but with
WCSs added.
Figure 27.
Air-Fi addressing example: WCIs and WCSs
Tracer SC+
group 1
WCI
WCI
GRP NET
NET
GRP NET
1
1
1
1
1
WCI
WCI
WCI
GRP NET
GRP NET
GRP NET
1
2
1
2
1
2
WCI
WCI
WCI
GRP NET
GRP NET
GRP NET
2
1
2
1
2
1
WCI
WCI
WCI
GRP NET
GRP NET
GRP NET
2
2
2
2
2
2
WCI
GRP
1
Tracer SC+
group 2
Sn: 1
UC: 101
Network 2
Network 1
Network 1
Network 2
Sn: 1
UC: 102
Sn: 1
UC: 201
Sn: 1
UC: 202
Sn: 1
UC: 301
Sn: 1
UC: 302
Sn: 1
UC: 401
Sn: 1
UC: 402
Sn: 2
UC: 402
gn: 11
gn: 11
gn: 12
gn: 12
gn: 21
gn: 21
gn: 22
gn: 22
gn: 22
Group and
network
addresses
must match.
Controller
addresses
must
match.
Sensor addresses default to 1. If multiple sensors are wired to a UC/BCI, each sensor must have a unique address.
UC/BCI 402 has two sensors
connected to it. Therefore,
the address of the second
sensor is set to “2.”
WCS
WCS
WCS
WCS
WCS
WCS
WCS
WCS
WCS
1
2 3 4
5
6
7
8
9
0
NET
GRP
1
2 3 4
5
6
7
8
9
0
WCI addressing
Controller
Controller
Controller
Controller
Controller
Controller
Controller
Controller
101
102
201
202
301
302
401
402