General Information
The step-by-step instructions outlined in this manual
describe the procedures required to successfully install an
AFDR retrofit air-cooled Adaptive Frequency Drive™
package in place of an existing starter on a Trane RTHD
helical rotary liquid chillers. This only applies to chillers
having a Tracer AdaptiView™ controller. If the RTHD chiller
has a CH530, it must be replaced with the Tracer
AdaptiView™ RTHD rotary chiller display upgrade kit
(RCDA; sold separately).
The AFDR can be ordered as a close floor mount, remote
floor mount, or remote wall mount. Voltage options
include 460/480 volts, 380/400 volts, and 575/600 volts.
D-Frame size AFDH drive packages can be ordered in a
unit-mounted, stand-mounted, or remote floor-mounted
cabinet configuration. The AFDR units can be equipped
with a drive having a maximum rating of 190 amps,
240 amps, 302 amps, 361 amps, 443 amps, or 535 amps
for 460V/480V, and 131 amps, 155 amps, 193 amps,
242 amps, 344 amps, or 400 amps for 575V/600V.
Other Literature Required Before Ordering
or Installing an AFDR Retrofit
This manual must be used in conjunction with the
following publications:
•
RTHD-SVX01*-EN (
Installation, Operation, and
Maintenance: Optimus™ Water-Cooled Chillers -
Model RTHD
)
•
BAS-SVP04*-EN (
Programming Guide: TR200
)
•
BAS-SVX54*-EN (
Operating Instructions: TR200 New
D-Frame, 110–400kW
)
•
RCDA-SVN001*-EN (
Installation Instructions: Tracer
AdaptiView™ RTHD Rotary Chiller Display Upgrade
Kit
)
Note:
Instructions provided in RCDA-SVN001*-EN
directly impact AFDR installation; review
literature carefully!