Installation
AFDR-SVN001D-EN
45
Line Voltage
AFD Mounting—Pedestal Installation
(All Kits)
1. Remove the front cover of the pedestal base for easy
access to power wires Using safe lifting practices and
keeping the wires inside the drive enclosure, carefully
lower the drive onto the pedestal base.
2. After lowering the drive onto the pedestal, securely
fasten the drive to the base at all connection points at
the front and back of the base.
3. Connect all power wire and dedicated ground wire to
the drive according to the supplied schematics. AFD
termination location allows 2 wires per phase.
Table 9.
AFDR unit weights and heat rejection (460V/480V)
460V/480V Catalog
Max Amps
158 Catalog/
190 Maximum
200 Catalog/
240 Maximum
252 Catalog/
302 Maximum
301 Catalog/
361 Maximum
369 Catalog/
443 Maximum
446 Catalog/
535 Maximum
Weight (lb)
135
135
135
275
275
275
Heat Rejection (BTU/hr)
7708
9286
12370
12161
15566
19477
Table 10. AFDR unit weights and heat rejection (575V/600V)
575V/600V
Catalog Max
Amps
109 Catalog/
131 Maximum
129 Catalog/
155 Maximum
160 Catalog/
192 Maximum
202 Catalog/
242 Maximum
242 Catalog/
290 Maximum
287 Catalog/
344 Maximum
333 Catalog/
400 Maximum
Weight (lb)
135
135
135
275
275
275
275
Heat Rejection
(BTU/hr)
5939
7168
9037
10488
12701
15232
17154
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06*-EN.
Figure 59.
Figure 60.