Pre-Installation
26
AFDR-SVN001D-EN
Preparing Tracer TU on the
Service Computer
After this retrofit, the UC800 controller will communicate
with the TR200 drive via a dedicated Modbus™ Master
connection (independent of the IPC bus). A software
upgrade is required to support this. The following steps
detail how to obtain and install the necessary software
onto the service laptop computer.
1. Tracer™ TU service tool version 9.0.322 or newer is
required to re-program the chiller’s UC800. As of this
printing, this version of Tracer TU is available for
download at:
https://home.ingerrand.com/sites/
softwaredownloads/SitePages/TU.aspx
2. If it is not already present, install this version of Tracer
TU on the service computer.
3. After the correct version of Tracer TU is installed on the
service computer, return to the same page (see link
provided in
,
), and click the
UC800
Firmware
link.
In the screen that appears, click the
Latest
Version : Download
link to download an EXE file.
Run the application to select specific chiller products
and install the correct software versions for that
product.
Figure 20.