tousek
/ EN_ST-63_02 / 25. 03. 2020
- 17 -
G
inner photocell
(PHC-contact: terminals KL1 45/46)
Photocells
not active:
to be selected, if the inner photocell should not be triggered.
during closing reverse:
if the safety device is triggered during closing the gate reverses (opens). If automatic mode
is selected the gate closes after the pause time is over. If impluse mode is selected a new CLOSE impulse must be
given.
stop, opens after release:
if the safety device is triggered during opening or closing the motor stops until the device
is released. Then the gate opens. If automatic mode is selected the gate closes after the pause time is over. If impluse
mode is selected a new CLOSE impulse must be given.
during opening stop-then open:
if the safety device is triggered during opening the motor stops until the device
is released. Then the gate opens. (back area monitoring). If automatic mode is selected the gate closes after the
pause time is over. If impluse mode is selected a new CLOSE impulse must be given.
Photocells
Connections and adjustments
G
outer photocell
(PHC-contact: terminals KL1 45/48)
Photocells
not active:
to be selected, if the outer photocell should not be triggered.
during closing reverse:
if the safety device is triggered during closing the gate reverses (opens). If automatic mode
is selected the gate closes after the pause time is over. If impluse mode is selected a new CLOSE impulse must be
given.
stop, opens after release:
if the safety device is triggered during opening or closing the motor stops until the device
is released. Then the gate opens. If automatic mode is selected the gate closes after the pause time is over. If impluse
mode is selected a new CLOSE impulse must be given.
Important: Photocells notes
Photocell connection:
• the control unit has a power supply connection for
a
24V a.c.
photocell (PHC)
power supply:
PHC-transmitter: terminals KL1 41/42
PHC-receiver:
terminals KL1 43/44
Note:
in „gate closed“ position the terminals 41/42 and 43/44 are being
switched into energy saving mode (no current).
• The PHC contacts have to be closed when using powered and posi-
tioned photocells (opening contact)
PHC-contacts
: inside = term. KL1 45/46, outside = term. KL1 45/48,
back area = term. KL1 45/49
Mounting note (SYNC function):
IMPORTANT:
When using two pairs of photocells please do not
install both photocell transmitters/receivers on the same side (to
eleminate interference between both) !
Exception:
photocells with
SYNC
function allow the installation of
both photocell transmitters/receivers on the same side without causing
interference to each other.
Self-monitoring of photocells:
The control unit has a monitoring function for the connected photocells. A test will be triggered by each impulse
and will be checked if the receiver of the photocell responds to the signal from the photocell transmitter. If the-
re is no communication between the photocell receiver and transmitter the control unit responds with an error.
The deactivation of the self-test function is only permitted if the safety installations correspond to the
category 3 !
you will find detailed information in the corresponding photocell manual.
1
2
3
3
left right
INSIDE
(1)
inner photocell
(2)
outer photocell
(3)
back area photocell
standard
transmitter1 receiver1
receiver2 transmitter2
with SYNC
transmitter1 receiver1
transmitter2 receiver2
All the photocells are activated by default (inside/outside/back area) in the menu. But it can be deactivated while
basic settings are carried out.