– 98 –
11. REPLACEMENT OF THE SERVICE P.C. BOARD
11-1. Interface (CDB) P.C. BOARD MCC-1675 (4316V693)
1. Setting the jumper wires
Model switching (J800 to J803)
Since this service P.C. board is available for several models, cut the jumper wires according to the following
table.
If they are not cut correctly, a check code “L10” or “L29” appears on the remote controller and the operation
of the air conditioner is disabled.
Function
Part name
Setting
Model switching
Jumper wire J800 ~ J803
Cut these jumper wires according to
the following table.
J 800
J 801
J 802
J 803
Model name
Factory setting (default)
RAV-GM2241AT
∗
-
∗∗
RAV-GM2801AT
∗
-
∗∗
O
:Connected,
×
:Cut
O
×
O
O
×
O
O
O
×
O
O
O