– 100 –
13. DETACHMENTS
No. Part name
Procedure
Remarks
c
Common
procedures
WARNING
Stop operation of the air conditioner and turn off breaker
switch.
CAUTION
Ensure wearing of gloves when performing any work in
order to avoid injury from parts, etc.
1. Detachment
1) Stop operation of the air conditioner, and turn off the
main switch of the breaker for air conditioner.
2) Remove the front panel. (3 pcs, Ø4 ×10 hexagonal
screws)
(1) After removing the screws slide the front panel
downwards.
(2) Pull the front panel forwards and then loosen the
right claw.
(3) Pull the front panel to the right, loosen the left claw,
and then remove the front panel.
3) Remove the terminal cover. (2 pcs, Ø4 ×8)
4) Remove the power and indoor/outdoor connection
wires from the wire clamps and terminals.
5) Remove the top cover. (6 pcs, Ø4 ×10 hexagon
screws)
2. Attachment
1) Attach the top cover. (6 pcs, Ø4 ×10 hexagon screws)
2) Connect the power and indoor/outdoor connection
wires to the terminal and fix in place using the code
clamps.
NOTE
The power and indoor/outdoor connection wires should be
fixed in place along the crossing pipes using commercially
available code clamps so as to avoid any contact with the
compressor, gas side valve, gas side piping, and
discharge pipe.
3) Attach the front panel. (3 pcs, Ø4 ×10 hexagon screws)
Remove the
screws
Loosen the
screws
Terminal cover
Front panel
Right claw
Right claw
Left claw
Left claw
Right claw
Left claw
Top cover
(1)
(3)
(2)