– 46 –
3-2. Heating fan control
1) Heating operations of the outdoor fan are controlled by a TE sensor, TO sensor and the compressor
revolution number.
(Control from a minimum W1 to a maximum is performed according to the table below).
2) Operation is fixed for 3 minutes after start up by a maximum fan tap corresponding to the zones in the
table below. Thereafter fan control is performed using the temperature from the TE sensor.
3) When TE
≥
24°C continues for 5 minutes, the compressor is stopped. The compressor is placed in the
same state as a normal thermostat OFF without a check code display.
The compressor is restarted after approximately 2 minutes 30 seconds and such interrupted operation
does not constitute a trouble.
When the operation in 3) above is frequently performed, the filter of the intake section of the indoor unit
may require cleaning.
Therefore restart operation after cleaning the filter.
GM280
Less than
38 rps
38rps or more
and less than 52rps
52rps
or more
Maximum
WA
WC
WF
WF
WF
WF
-2 taps/20sec
stop timer count
(Until W1)
-2 taps/20sec
(Until W1)
WC
WF
WF
WF
WF
WF
WA
WA
WF
WF
WF
WF
15
18
21
24
-2 taps/20sec
(Until W1)
Revolution number HOLD
+1tap /20sec
10˚C
≤
TO
5˚C
≤
TO < 10˚C
-3˚C
≤
TO < 5˚C
-10˚C
≤
TO < -3˚C
TO < -10˚C
TO trouble
GM224
Less than
38 rps
38rps or more
and less than 52rps
52rps
or more
Maximum
WA
WC
WC
WF
WF
WF
-2 taps/20sec
stop timer count
(Until W1)
-2 taps/20sec
(Until W1)
WC
WC
WF
WF
WF
WF
WA
WA
WC
WF
WF
WF
15
18
21
24
-2 taps/20sec
(Until W1)
Revolution number HOLD
+1tap /20sec
10˚C
≤
TO
5˚C
≤
TO < 10˚C
-3˚C
≤
TO < 5 ˚C
-10˚C
≤
TO < -3˚C
TO < -10˚C
TO trouble