– 109 –
No. Part name
Procedure
Remarks
j
PMV coil
1. Detachment
1) Following to work of item 1 of
c
.
2) Remove the coil from the PMV body by rotating the coil
(about 45°) while drawing the coil upward.
2. Attachment
1) Fix the coil positioning protrusions securely in the
concavities of the PMV body so that the PMV leads are
on the front right side.
k
Fan guard
1. Detachment
1) Following to work of item 1,
d
, and
e
of
c
.
NOTE
Do the work on cardboard or a cloth etc. spread out to
prevent the product from being scratched.
2) Remove the outlet cabinet and place the fan guard
side facing down.
3) Remove the claws (8 places) of the fan guard.
2. Attachment
1) Hook the hooks from the front side and press the claws
(8 places) by hand to fix them in place.
NOTE
Ensure that all the claws are fixed in their specified position.
l
[Reference]
Sensor
mount
positions
Outlet cabinet claws
Claw
Fan guard
PMV coil
PMV lead
(About 45˚)
(About 45˚)
TL sensor
TS sensor
TE sensor
TD sensor
TO sensor
1) TD sensor: discharge pipe
2) TL sensor: heat exchanger upside
3) TS sensor: 4-way valve - between accumulator
4) TE sensor: lowest capillary joint
5) TO sensor: Heat exchange surface