– 45 –
3. Outdoor fan revolution number control
Control of fan revolution number and the fan taps in this unit are shown below.
Fan Taps Revolution number Allocation [rpm]
3-1. Cooling fan control
1) Cooling operations of the outdoor fan are controlled by a TL sensor, TO sensor and the compressor
revolution number. Control is performed per 1 tap of DC fan control.
The outdoor fan is controlled by every 1 tap of DC fan control (14 taps).
During startup, operation is fixed for 60 seconds by a maximum fan tap corresponding to the zones shown
in the table below. Thereafter fan tap is controlled by a temperature outputted from the TL sensor.
W1
W2
W3
W4
W6
W7
W8
W9
WA
WB
WC
WD
WE
WF
GM224
GM280
200
0
200
0
Upper Fan
Lower Fan
Upper Fan
Lower Fan
240
0
240
0
340
380
340
380
430
470
430
470
500
540
500
540
580
610
580
610
640
680
640
680
680
720
680
720
720
760
720
760
760
800
760
800
820
860
820
860
860
900
860
900
910
950
910
950
960
1000
960
1000
W5
460
500
460
500
GM280
Less than 38rps
38rps or more
and less than 52 rps
52rps or more
38˚C
≤
TO
29˚C
≤
TO < 38˚C
15˚C
≤
TO < 29˚C
5˚C
≤
TO < 15˚C
0˚C
≤
TO < 5˚C
-5˚C
≤
TO < 0˚C
TO < -5˚C
TO trouble
Min.
W6
W5
W3
W2
W1
W1
OFF
OFF
Max.
WB
WA
W7
W5
W3
W2
W2
WB
Min.
W8
W7
W5
W4
W3
W2
W1
W1
Max.
WF
WF
W9
W7
W5
W4
W3
WF
Min.
WA
W9
W7
W6
W4
W3
W2
W2
Max.
WF
WF
WB
W9
W7
W5
W4
WF
TL
Revolution number HOLD
WF tap
58
+1tap/20sec
55
37
34
GM224
Less than 38rps
38rps or more
and less than 52 rps
52rps or more
38˚C
≤
TO
29˚C
≤
TO < 38˚C
15˚C
≤
TO < 29˚C
5˚C
≤
TO < 15˚C
0˚C
≤
TO < 5 ˚C
-5˚C
≤
TO < 0 ˚C
TO < -5˚C
TO trouble
Min.
W6
W5
W3
W2
W1
W1
OFF
OFF
Max.
WB
WA
W7
W5
W3
W2
W2
WB
Min.
W8
W7
W5
W4
W3
W2
W1
W1
Max.
WE
WD
W9
W7
W5
W4
W3
WE
Min.
WA
W9
W7
W6
W4
W3
W2
W2
Max.
WE
WD
WB
W9
W7
W5
W4
WE
TL
Revolution number HOLD
WF tap
58
+1tap/20sec
55
37
34